enthalpy sample 3

Measured by
Austrian Institute of Technology
Measured with NETZSCH DSC 204F1 Phoenix
Measured according to standard
Task 4229 PCM DSC procedure
Comment on measurement
Crucible: Al. pan, closed. Purge gas: Nitrogen. Number of heating & cooling cycles: 3.
Reference
Heating rate
0.25 K/min
Cooling rate
0.25 K/min
Sample mass
10.3 mg
 
Endothermic heat flow Exothermic heat flow
Value Uncertainty Value Uncertainty
Enthalpy
202.84 kJ/kg
0.85 kJ/kg
200.44 kJ/kg
0.32 kJ/kg
Integration lower limit
25.47 °C
26.27 °C
Integration upper limit
28.77 °C
24.63 °C
Onset temperature
27.1 °C
0 K
26.03 °C
0.07 K
Endset temperature
28.5 °C
0 K
25.17 °C
0.07 K
Octadecane: Heating/cooling enthalpy measurement 1
Octadecane: Heating/cooling enthalpy measurement 2
Octadecane: Heating/cooling enthalpy measurement 3

Octadecane: Heating/cooling enthalpy measurement 1

Octadecane: Heating/cooling enthalpy measurement 1

Octadecane: Heating/cooling enthalpy measurement 2

Octadecane: Heating/cooling enthalpy measurement 2

Octadecane: Heating/cooling enthalpy measurement 3

Octadecane: Heating/cooling enthalpy measurement 3